Lighting Relays from Cristal Offers Energy Savings

Cristal

The WR-6161-CC lighting relay from Cristal allows control of lighting system or any other application within its specifications and can easily be controlled with a low voltage supply (24 Vac). The WR-6161-CC relays require only a momentary pulse to change the state and requires no energy to maintain the state.

Features

  • 24 Vac rectified momentary command
  • 1 line voltage output
  • 1 low voltage output
  • Mechanical status indicator
  • ON/OFF manual bypass control

Operation

  • A negative pulse turns the relay ON and a positive pulse turns it OFF. Using a diode, an AC signal can be rectified to turn the relay either ON or OFF.
  • The relay has 2 similar diodes built inside that are in series with the relay coil. The diodes in the relay act as gates for the switch signal.
  • To turn the relay ON or OFF, the rocker switch completes the circuit by selecting the ON or OFF diodes. If the diode selected is in the same direction as the gate diode in the relay, the relay will switch. If the gate diode is not in the correct direction, then nothing will happen since the relay is already in the correct state for the action selected by the switch. When the switch is released, a spring returns it to the central neutral position.
  • Indication (ON state) and location (OFF state) are obtained by utilizing LED diodes built into the switch. Only the LED which is connected in the same direction as the gate diode in the relay will light. The maximum number of LED switches that can be connected to the same relay is 4.

Specifications

Operating Control Voltage
  • 18 Vac to 30 Vac rectified positively or negatively
  • State shift time delay (1 typical cycle, 3 cycles maximum)
  • Positive pulse (Relay OFF)
  • Negative pulse (Relay ON)
Output
  • WR-6161-CC General Use 20A to 347 Vac
  • Engine (1/2 HP 120 Vac or 1-1/2 HP to 277 Vac)
  • Standard Ballast (20A to 347 Vac)
  • Electronic Ballast (16A to 120/277 Vac)
  • SCCR (14 000A to 277Vac)
Testing Conditions
  • Switching Cycle 20 Times/Minute
  • More than 60 000 ON/OFF operation
Operating Temperature
  • -30°C to 40°C (Ambient Temperature)
Dimensions
  • 2.4’’ (height) x 3.8’’ (length) x 0.98’’ (width)

More information about the WR-6161-CC lighting relays from Cristal

WR-6161-CC lighting relays data sheet

Related Articles


Latest Articles

  • WAC Group’s Tony Wang to Receive Icon Award

    WAC Group’s Tony Wang to Receive Icon Award

    Tony Wang, chairman and founder of New York-based WAC Lighting, will receive the Long Island Business News (LIBN) Icon Honor Award this month. In 1984, Tony and his wife, Tai, established Wangs Alliance Corporation d/b/a WAC Lighting (now WAC Group), which has evolved into a lighting industry leader. LIBN’s Icon Honors recognize Long Island-based business Read More…

  • In Memoriam: Michael Doyle Leech of Stuart C. Irby Co.

    In Memoriam: Michael Doyle Leech of Stuart C. Irby Co.

    Michael Doyle Leech, age 72 of Franklin, Tenn., passed away on February 16, 2026. Rob Taylor, President of Sonepar Americas (which includes Irby) said, “Mike was a proud veteran and a devoted family man, qualities that shaped the way he led, served, and cared for the people around him. Few people have embodied dedication and Read More…