Lighting Relays from Cristal Offers Energy Savings

Cristal

The WR-6161-CC lighting relay from Cristal allows control of lighting system or any other application within its specifications and can easily be controlled with a low voltage supply (24 Vac). The WR-6161-CC relays require only a momentary pulse to change the state and requires no energy to maintain the state.

Screenshot 2025 04 18 At 6.44.02 PM 1024x706

Features

  • 24 Vac rectified momentary command
  • 1 line voltage output
  • 1 low voltage output
  • Mechanical status indicator
  • ON/OFF manual bypass control

Operation

  • A negative pulse turns the relay ON and a positive pulse turns it OFF. Using a diode, an AC signal can be rectified to turn the relay either ON or OFF.
  • The relay has 2 similar diodes built inside that are in series with the relay coil. The diodes in the relay act as gates for the switch signal.
  • To turn the relay ON or OFF, the rocker switch completes the circuit by selecting the ON or OFF diodes. If the diode selected is in the same direction as the gate diode in the relay, the relay will switch. If the gate diode is not in the correct direction, then nothing will happen since the relay is already in the correct state for the action selected by the switch. When the switch is released, a spring returns it to the central neutral position.
  • Indication (ON state) and location (OFF state) are obtained by utilizing LED diodes built into the switch. Only the LED which is connected in the same direction as the gate diode in the relay will light. The maximum number of LED switches that can be connected to the same relay is 4.
Screenshot 2025 04 18 At 6.44.07 PM 1024x785

Specifications

Operating Control Voltage
  • 18 Vac to 30 Vac rectified positively or negatively
  • State shift time delay (1 typical cycle, 3 cycles maximum)
  • Positive pulse (Relay OFF)
  • Negative pulse (Relay ON)
Output
  • WR-6161-CC General Use 20A to 347 Vac
  • Engine (1/2 HP 120 Vac or 1-1/2 HP to 277 Vac)
  • Standard Ballast (20A to 347 Vac)
  • Electronic Ballast (16A to 120/277 Vac)
  • SCCR (14 000A to 277Vac)
Testing Conditions
  • Switching Cycle 20 Times/Minute
  • More than 60 000 ON/OFF operation
Operating Temperature
  • -30°C to 40°C (Ambient Temperature)
Dimensions
  • 2.4’’ (height) x 3.8’’ (length) x 0.98’’ (width)

More information about the WR-6161-CC lighting relays from Cristal

WR-6161-CC lighting relays data sheet

Related Articles


Latest Articles

  • WAC Group Appoints Executive Director of Business Development – Commercial

    WAC Group Appoints Executive Director of Business Development – Commercial

    Ryan Radke is a veteran of the commercial and architectural lighting arena. New York-based WAC Group has appointed Ryan Radke as Executive Director of Business Development – Commercial. In this role, he will lead strategic growth initiatives and manage key customer and sales representative relationships across the commercial channel. According to WAC Group Vice President… Read More…

  • Solais Lighting Appoints Al Near as Chief Commercial Officer

    Solais Lighting Appoints Al Near as Chief Commercial Officer

    Longtime industry leader and trusted Solais partner joins executive team to help drive the company’s next stage of expansion Texas-based Solais Lighting has named Al Near as Chief Commercial Officer (CCO). He joins the architectural-grade lighting solutions provider after more than 30 years in the lighting and controls industry, where he has held leadership roles… Read More…